No Slide Title

Report
Vista-20P Series
WebCast
 Honeywell.com
Introduction
• This course will cover programming and features on the
Vista-20P throughout, with several slides that explain
and compare the Vista-20P with the Vista-10P and
Vista-15P.
Honeywell Proprietary
 Honeywell.com
Series Comparison
Max Zones
Standard wired zones
Zone Doubling
Max Wired Expansion
Max Wireless (5800)
Keyfob zones
Programmable outputs
on-board Voltage triggers
Zone Lists
Pager Support
Event Log
User Codes
AUI consoles
Vista-20P
48
8
15
40
40
16
16
2
12
Vista-15P
32
6
0
22
26
8
8
2
10
Vista-10P
22
6
0
0
16
8
4
2
9
4
100
48
4
2
50
33
2
1
32
16
0
Honeywell Proprietary
 Honeywell.com
Agenda
•
•
•
•
•
•
•
Basic Panel Features
Mechanics of Programming
Programming Locations
*56 Zone Programming
*79 Output Device Mapping
*80 Defining Output Functions
Security Codes – Authority Levels & Special Features
Honeywell Proprietary
 Honeywell.com
Features
•
•
•
•
•
•
•
•
•
Unvacated auto stay
Cross zoning
Night arming
Carbon monoxide zone type
Dynamic zone type
Scheduling
Vent Zone
Automatic Periodic Test Command
SIA compliant
Honeywell Proprietary
 Honeywell.com
ANSI/SIA CP-01-2000
A FALSE ALARM REDUCTION standard, calls for
manufacturer’s to default control panels as follows:
•60 second exit delay
•30 second entry delay plus 30 second dialer delay
•Auto Stay arming enabled
•Cancel verify option is enabled (displays on keypad)
•Swinger suppression defaulted to 1 report per zone
per armed period
Honeywell Proprietary
Vista-20P Series
Mechanics of Programming
 Honeywell.com
Mechanics of Programming
• Entering Program Mode - Use one of the following methods to
enter Programming Mode:
1. Press both the [*] and [#] keys at the same time, within 50 seconds
after power is applied to the Control.
2. After power-up, enter the Installer Code (4112) + 800
(If *98 was used to exit previously, method 1 above must be used
to enter the program mode again)
Note: When connecting a console to a defaulted panel, the console
must be set to address 16. This will be covered later.
Honeywell Proprietary
 Honeywell.com
Defaulting
• To default the panel you will enter:
–[*]+9+7
– Upon entering programming for the first time, it is recommended
that you default the panel.
• To set the panel for first time communication with Compass
Downloading Software you will enter:
–[*]+9+6
• CSID = FFFFFFFF
• Primary Subscriber Account Number = FFFF
Note: If your downloader requires a call back phone
number, refer to field *94 in your programming form.
Honeywell Proprietary
 Honeywell.com
Mechanics of Programming
* 20 Installer Code
[4112]
Enter 4 digits, 0 – 9
To change the Installer’s Code you would enter Programming mode,
then press *20, then the new code.
To view what is in field 20 you would enter #20, the panel will display
the location contents one digit at a time.
Honeywell Proprietary
 Honeywell.com
Mechanics of Programming
• Exiting Program Mode:
*98 prevents re-entry into the Programming modes
using the Installer Code.
*99 allows re-entry into the Programming modes
using Installer Code (4112) + 800
Note: If *98 is used to exit programming mode, the system must be
powered down, AC and Battery, then press * & # simultaneously within
50 seconds of power up to re-enter programming.
Honeywell Proprietary
Vista-20P Series
Programming Locations
 Honeywell.com
Entry/Exit Programming
*34 Exit Delay
[ 60,60 ]
Part. 1
Part. 2
00 - 96 = 0-96 Sec.
97 = 120 Sec.
[ 30,30 ]
*35 Entry Delay #1
Part. 1
Part. 2
00 - 96 = 0-96 Sec.
97 = 120 Sec.
98 = 180 Sec.
99 = 240 Sec.
[ 30,30 ]
*36 Entry Delay #2
Part. 1
Part. 2
Same entry choices as *35
Honeywell Proprietary
 Honeywell.com
Communication Programming
…
*41 Primary Phone Number
Enter up to 20 digits
*42 Second Phone Number
…
Enter up to 20 digits
*43 P1 Primary Account Number
4 or 10 Digits
[ FFFF ]
4 or 10 Digits
[ FFFF ]
*44 P1 Second Account Number
Honeywell Proprietary
 Honeywell.com
Communication Programming
*45 P2 Primary Account Number
4 or 10 Digits
[ FFFF ]
4 or 10 Digits
[ FFFF ]
*46 P2 Second Account Number
[ 7,7 ]
*48 Report Format
Prim.
Sec.
0 = 3+1, 4+1 Ademco L/S Stand. 6 = 4+2 Ademco Express
1 = 3+1, 4+1 Radionics Stand.
7 = 4-digit Ademco Contact ID
2 = 4+2 Ademco L/S Stand.
8 = 3+1, 4+1 Ademco L/S Stand.
3 = 4+2 Radionics Stand.
9 = 3+1, 4+1 Radionics Expanded
5 = 10-Digit Ademco Contact ID
Honeywell Proprietary
 Honeywell.com
Backup Communications
*29 Long Range Radio Output
[0]
0 = No
1 = Yes
*29 Menu Mode for IP/GSM Enable (rev 7+)
This is a Menu Mode command, not a data field, for programming IP/GSM options.
Enable IP/GSM?
0= NO 1=YES
1=PROG 2=DIAG
0=QUIT
Enable INT IP/GSM?
0 = no, not using either IP or GSM
1 = yes, Using IP and/or GSM module
[*] to continue
Programming/Diagnostics Select
1 = Prog (program the IP/GSM options)
2 = Diag (enter diagnostic mode) Do not select if
using an external comm device
0 = Quit; returns to data field programming mode
Honeywell Proprietary
 Honeywell.com
*29 Menu Mode Keypad Functions
Internal Device Programming Prompts
[∗] = scroll the options of a particular prompt
[#] = accept the entry and move to the next prompt
[A] = backspace or shift-[A] for escape
[B] = scroll to next prompt or shift-[B] scroll to previous prompt
[C] = answer No or shift-[C] answer Yes to prompt
[D] = shift key
Honeywell Proprietary
 Honeywell.com
Backup Communications
*54 Dynamic Signaling Delay
[0]
0 = No delay (Both signals sent)
1-15 = delay times in 15 sec. increments
1 = 15 Sec. 2 = 30 Sec. Etc.
Note: if *55 is set to “0”, use min. 30 sec
to avoid redundant IP report.
*55 Dynamic Signaling Priority
[0]
0 = Primary Dialer first
1 = IP/GSM module first
Honeywell Proprietary
 Honeywell.com
System Setup
*84 Auto Stay Arm
[1] 0=no, 1=partition 1 only
2=partition 2 only, 3=both
partitions
If enabled, the system will automatically change AWAY mode to STAY
mode if the entry/exit door is not opened and closed within the exit
delay time after the user arms in AWAY mode from a wired keypad.
*85 Cross Zone Timer
[0] 0=15 sec.
(Assign cross zones on zone
list 4, with *81 Menu mode)
(see program sheet for complete list of options)
*93 Reports in Armed
Period Per Zone
[1] 0=Unlimited Reports
1=1 report per
2=2 reports per
Honeywell Proprietary
 Honeywell.com
Pager Information
….
*160 Pager 1 Phone No.
Enter up to 20 digits
7-digit status code: XXX-YYYY
XXX = 3-digit event code:
911 = Alarm
811 = Trouble
101 = Opening (disarm)
102 = Closing (arm AWAY
YYYY = 4-digit user or zone number
The first digit indicates the partition, followed by the 3-digit
user or zone number.
0 = system, 1 = part 1
2 = part 2, 3 = part 3
….
*161 Pager 1 Characters
Enter up to 16 digits
The character could be composed of:
• PIN number
• Subscriber account number
• * (enter # + 11 to send *)
• # (enter # + 12 to send #)
• Pause (enter # + 13 to allow a 2-second pause)
Honeywell Proprietary
 Honeywell.com
Pager Options
*162 Pager 1 Reporting Options
[ 0,0,0 ]
Part. 1 Part. 2 Common
0 = no report sent
1 = open/closes all users
4 = All alarms and troubles
12 = Alarms/troubles for zones entered in zone list 9
13 = Alarms/troubles for zones entered in zone list 9 and open/close for all users
Pagers 2-4 are set up the same way in Locations *163 -*171
Honeywell Proprietary
 Honeywell.com
Pager Options
*172 Pager Delay Option for Alarms
[3]
0 = none
1 = 1 minute
2 = 2 minutes
3 = 3 minutes
This delay is for ALL pagers in the system.
Honeywell Proprietary
 Honeywell.com
Configurable Zone Type Programming
*182 Configurable Zone Type 90
1
2
3
4
5
6
7
8
9
10
See programming sheet for complete List of options.
*183 Zone Type 90 Report Codes
90 Alarm ID XXX
Trouble ID:XXX
Enter the desired 3-digit Contact ID report codes for alarms
and troubles occurring on zones assigned to this zone type.
*184 Configurable Zone Type 91
1
2
3
4
5
6
7
8
9
10
See programming sheet for complete List of options.
*185 Zone Type 91 Report Codes
91 Alarm ID XXX
Trouble ID:XXX
Enter the desired 3-digit Contact ID report codes for alarms
and troubles occurring on zones assigned to this zone type.
Honeywell Proprietary
 Honeywell.com
Advanced User Interface Programming
[1] [1] [0] [0]
*189 Symphony (AUI) enable
AUI 1 AUI 2 AUI 5 AUI 6
Enter each AUI’s Home partition.
0 = disabled
1 = partition 1; 2 = partition 2
3 = partition 3 (common)
Note: an external power supply may
be required when using AUI consoles.
Honeywell Proprietary
 Honeywell.com
Keypad Options
NOTE: Options for keypad address 16 are set by
the factory and cannot be changed.
Each keypad must be assigned a unique address.
*190 Keypad 2 Address 17
[0]
[0]
Partition/Enable
Sound
0 = keypad disabled;
1-3 = part.no. (3=common)
0 = no suppression
1 = suppress arm/disarm and E/E beeps
2 = suppress chime beeps only
3 = suppress arm/disarm, E/E, and chime beeps
*191 – *196 Are Identical for addresses 18 – 23 respectively.
Honeywell Proprietary
 Honeywell.com
Keypad Options
*197 Exit Time Display Interval
[0]
0 = no display
1-5 = seconds between display refresh
*198 Display Partition Number
(for Alpha Display Keypads)
[0]
0= no; 1=yes
(partition number appears on Alpha Display)
*199 ECP Fail Display
[0]
0 = 3-digit display (“1” + device address)
1 = 2-digit fixed-display as “91”
Honeywell Proprietary
Vista-20P Series
ECP Addressing
 Honeywell.com
Table of Device Addresses
All devices attached to ECP (keypad) terminals must be addressed.
Depending on the device and its function the address is determined by the following:
Address
Keypad
Message††
Device
00
100/91
RF Receiver
01
N/A
AUI 1
02
N/A
AUI 2
03
103/91
Long Range Radio
04
104/91
4286 Voice Module
05
N/A
AUI 5
06
N/A
AUI 6
107/91
108/91
109/91
110/91
111/91
Zone Expanders (4219/4229)
Module 1 zones 09-16
Module 2 zones 17-24
Module 3 zones 25-32
Module 4 zones 33-40
Module 5 zones 41-48
07
08
09
10
11
Honeywell Proprietary
 Honeywell.com
Table of Device Addresses
Keypad Message††
Device
112/91
113/91
114/91
115/91
Relay Modules (4204)
Module 1
Module 2
Module 3
Module 4
16-23
N/A
Keypads
Keypad 1 – 8
28
N/A
5800TM module
Address
12
13
14
15
†† Addressable devices are identified by “1” plus the device
address when reporting. Enter a report code for zone 91 to enable
addressable device reporting (default = reports enabled). See field
*199, mentioned earlier, for ECP Fail Display options.
Honeywell Proprietary
Vista-20P Series
Zone Programming
*56 Menu Mode
 Honeywell.com
*56 Zone Programming Mode
Confirm?
SET TO CONFIRM?
0= NO 1=YES
Enter Zn Num.
(00 = Quit)
0
10
Zn ZT P RC In: L
10 00 1 10 RF 1
0 = no
1= yes
Enter Zone Number
01-99 = zone number
00 = quit
[*] to continue
Not all numbers
Available.
Summary Screen
[*] to continue
Or
Zn ZT P RC
10 00 1 10
In: AD
AW: 07
Or
IN: L = Wireless, RF = Supervision
IN: AD = Expansion, AW = Aux wired
HW: RT = Hard Wire, EL = loop type
Zn ZT P RC HW: RT
02 00 1 10 EL 1
Honeywell Proprietary
 Honeywell.com
*56 Zone Programming Mode
10 Zone Type
Perimeter
03
Zone Type (ZT)
00 = Not Used
01 = Entry/Exit #1
02 = Entry/Exit #2
03 = Perimeter
04 = Interior Follower
05 = Day/Night
06 = 24-Hr Silent
07 = 24-Hr Audible
08 = 24-Hr Aux
09 = Fire
10 = Interior w/Delay
12 = Monitor Zone
14 = Carbon Monoxide
16 = Fire w/Verify
20 = Arm-Stay*
21 = Arm-Away*
22 = Disarm*
23 = No Alarm Response
24 = Silent Burglary
77 = Keyswitch
81 = AAV Mon. Zone
90-91 = Configurable
* 5800 button-type transmitters only.
Honeywell Proprietary
 Honeywell.com
*56 Zone Programming Mode
Partition No. (P) 1-3 = partition (3=Common)
10 Partition
[*] to continue
1
10 Report Code
1st 01 2nd 00
02 Hardwire Type
EOL
Report Code (RC)
10
01-09, 10 for 0, 11 for B, 12 for C, 13 for D, 14 for E,
15 for F. 00 to Disable
Examples: 01 00 = report code 10
13 15 = report code DF
Hardwire Type
0
0=EOL; 1=NC; 2=NO; 3=zone doubling (ZD);
4=double-balanced (DB). This prompt appears
only for zone numbers 02-08.
[*] to continue
Honeywell Proprietary
 Honeywell.com
*56 Zone Programming Mode
Response Time (RT)
02 Response Time
1
0 = 10mSec; 1 = 350mSec;
2 = 700mSec; 3=1.2 seconds
[*] to continue
Only for zones 01-08, zone 02 shown
Input Device type (In)
10 Input Type
RF Trans
3
2 = AW (Aux wired zone)
3 = RF (supervised RF transmitter)
4 = UR (unsupervised RF transmitter)
5 = Button type RF transmitter (unsupervised)
10 Input S/N:
A XXX-XXXX
L
1
Serial number Entry and Loop Number Entry
Used only when enrolling wireless transmitters.
a. Transmit two open/close sequences.
b. Manually enter the 7-digit serial number.
c. Press key [C] to copy the serial number previously
enrolled.
[*] to continue
Honeywell Proprietary
 Honeywell.com
*56 Zone Programming Mode
10 Input S/N:
A 022-4064
L
?
10 Input S/N:
A 022-4064
L
1
10 XMIT TO CONFIRM
PRESS * TO SKIP
Loop Number Change
Enter the loop number.
To delete enter 0 in the loop number.
[*] to continue
Enroll Summary
If the serial/loop number combination is not a duplicate
in the system, a display showing the serial number and
loop number entry will appear.
[*] to continue
Confirm
Note: This prompt will only appear if the first
prompt after entering *56 was answered “YES”
[*] to continue
Honeywell Proprietary
 Honeywell.com
*56 Zone Programming Mode
Entd
Rcvd
A022-4063
A022-4064
Zn ZT P RC In: L
10 03 1 10 RF 1
Not Confirmed
[*] to continue
If the serial number transmitted does not match
the serial number entered this prompt will
appear.
Summary Screen
[*] to continue
Honeywell Proprietary
Vista-20P Series
Output Programming
 Honeywell.com
Output Device Option
*177 Device Duration 1,2
(used in *80 menu mode-Device Actions 5/6)
0 = 15 secs
1 = 30 secs
2 = 45 secs
3 = 60 secs
4 = 90 secs
5 = 2 min
6 = 2-1/2 min
7 = 3 min
[0] [0]
1
2
8 = 4 min
9 = 5 min
# = 10 = 6 min
# + 11 = 7 min
# +12 = 8 min
# + 13 = 10 min
# + 14 = 12 min
# + 15 = 15 min
Honeywell Proprietary
Vista-20P Series
Output Device Mapping
*79 Menu Mode
 Honeywell.com
*79 Menu Mode
*79 Mode is used to identify available
outputs that the panel can use.
These outputs are actually
programmed to activate and release in
*80 defining output functions.
Honeywell Proprietary
 Honeywell.com
*79 Menu Mode
ENTER OUTPUT NO.
00 = QUIT
xx
Device Output Number
01-18 relays/X-10;
00 = Quit
[*] to continue
This is the reference relay number as used in the system.
Relays and X-10 devices are numbered 01-16.
The on-board triggers are numbered 17 and 18.
XX OUTPUT TYPE
DELETE
0
Output Type This prompt appears if selecting outputs 01-16.
0 = delete
1 = relay on 4204/4229 module
2 = Powerline / X-10
[*] to continue
If X-10 is selected, we will use “A” prompt
If relay is selected, we will use “B” prompt
Honeywell Proprietary
 Honeywell.com
*79 Menu Mode
“A”
Unit Number
XX UNIT No.
yy
If X-10 is selected, a prompt for the unit number
appears.
01-16 = predefined unit number
[*] to continue
Honeywell Proprietary
 Honeywell.com
*79 Menu Mode
Module Address
“B”
XX MODULE ADDR
07-15
yy
Module Address
07-15 = predefined address
[*] to continue
Address
Module
07
1st 4229 (with zones 09-16)
08
2nd 4229 (with zones 17-24)
09
3rd 4229 (with zones 25-32)
10
4th 4229 (with zones 33-40)
11
5th 4229 (with zones 41-48)
12
1st 4204
13
2nd 4204
14
3rd 4204
15
4th 4204
Honeywell Proprietary
 Honeywell.com
*79 Menu Mode
XX REL POSITION.
1-4
zz
ENTER OUTPUT NO.
00 = QUIT
xx
Relay Position
1-4 = relay position
[*] to continue
This is the physical relay position with respect
to the relay module upon which it is located.
The system then returns to the Output Number
prompt for programming the next device.
Honeywell Proprietary
 Honeywell.com
*79 Menu Mode
17 OUT NORM LOW
0= NO 1=YES
0
Output Normally Low
0=no (standard default)
1=yes
[*] to continue
This prompt appears only for triggers 17 & 18.
Selecting 0 (no) sets the output level normally high(open).
Selecting 1 (yes) set the output level normally low(ground).
Output trigger 17 (100mA max.) can be used for resetting 4wire smoke detectors (up to 2 smokes) by connecting it to the
negative power terminal of the smoke detector.
Honeywell Proprietary
Vista-20P Series
Defining Output Functions
*80 Menu Mode
 Honeywell.com
*80 Menu Mode
In *80, we program relays or X-10 devices, previously defined in *79
output device mapping, to activate and deactivate.
The Vista-20P allows 48 output functions to be programmed.
The Vista-15P allows 24 output functions to be programmed.
The Vista-10P allows 12 output functions to be programmed.
Each output function determines only one action.
For example: To turn a relay on and off requires two output functions.
Honeywell Proprietary
 Honeywell.com
*80 Menu Mode
Output Funct. #
(00 = Quit)
01
Output Function No.
01 – 48 output function number
Enter the output function number to be defined
(or 00 to exit).
[*] to continue
01 A E P Trig
?00 0 0 - ZL=1
Summary Screen
A= Output Action; E= Triggering event;
P= Partition; Trig = Trigger type
[*] to continue
Note: A question mark in the summary screen
indicates that the device number shown has not
been mapped. Use *79 Menu mode to map the
device.
Honeywell Proprietary
 Honeywell.com
*80 Menu Mode
01 Activated by:
Delete
Delete?
0 = NO, 1 = YES
0
Activated By
0 = delete (delete the output function and any
previous programming; see prompt below
1 = zone list (go to “A” prompt)
2 = zone type (go to “B” prompt)
3 = zone number (go to “C” prompt)
[*] to continue
Press 1 to delete this output definition.
Honeywell Proprietary
 Honeywell.com
*80 Menu Mode
01 Activated by:
Zone List
1
“A”
01 Zn List
1
Enter Event
Alarm
1
Zone List
1 – 8 zone list
[*] to continue
0 = restore; 1 = alarm;
2 = fault; 3 = trouble
NOTE: For alarm, fault, and trouble an event on ANY
Zone in the list activates the output, but ALL zones in
the list must be restored before the output is restored.
Press [*] to continue to the “Output Action” prompt.
Honeywell Proprietary
 Honeywell.com
*80 Menu Mode
01 Activated by:
Zone Type
2
“B”
01 Enter Zn type
Perimeter
03
Zone Type
Enter the desired zone type:
There are a wide variety of zone types and
system operations available.
[*] to continue
Enter the partition in which this zone type will occur.
01 Partition
Any partition
0 = any partition; 1 = partition 1;
2 = partition 2; 3 = common
Press [*] to continue to the “Output Action” prompt.
Honeywell Proprietary
 Honeywell.com
*80 Menu Mode
01 Activated by:
Zone Number
3
“C”
01 Enter Zn No.
12
01 Enter Event
Restore
0
Zone Number
Enter the zone number desired
Press [*] to continue.
Enter the zone event that will activate this output.
0 = restore; 1 = alarm/fault/trouble
Press [*] to continue to the “Output Action prompt
Honeywell Proprietary
 Honeywell.com
*80 Menu Mode
01 Output Action
Close for 2 sec
Enter Output No.
R02
02
02 A E P TRIG
R02 1 1 3 ZL=1
Output Action 0 – 6
0 = off
4 = Change Device State
1 = Close for 2 seconds 5 = Duration 1 (see data field *177)
2 = Close and Stay Closed 6 = Duration 2 (see data field *177)
3 = Continuous Pulse on & off (1 sec ON, 1 sec OFF)
Output Number
01 – 16 = as defined in *79
17 – 18 = on-board triggers
Enter the device output number (as defined in *79) you
want associated with this output function.
Press [*] to continue
Summary Screen
Press [*] to continue
Honeywell Proprietary
Vista-20P Series
Test Report Setup
 Honeywell.com
Automatic Periodic Test Report
The system can be set to automatically send test reports (automatically
enables report code in field *64; Contact ID code 602) at specified
intervals.
The frequency of the report can be set in Scheduling mode (event 11) or
by the following key commands:
Installer code + [#] + 0 + 0 = test report sent every 24 hours
Installer code + [#] + 0 + 1 = test report sent once per week
Installer code + [#] + 0 + 2 = test report sent every 28 days
Each mode sets schedule 32, to the stated repeat option; the first test
report is sent 12 hours after command.
To ensure that test reports are sent at the times expected, set the RealTime Clock to the proper time before entering the test report schedule
command.
Honeywell Proprietary
 Honeywell.com
Setting the Real Time Clock
Enter [4-digit Installer or Master code] + # + 63
TIME/DATE SAT
12:00AM 01/01/00
TIME/DATE SAT
12:00A 2000/01/01
•Press the [*] key to change the Date/Time settings. The
blinking cursor appears on the first digit of the hour.
•Enter the time (hour, then minute). After each entry the
cursor moves to the right.
•Press any odd-digit for PM, or any even-digit for AM.
•Enter the 2-digit year, 2-digit month, and the 2-digit day
in sequence. The day of the week is automatically
calculated and displayed based on the date entered.
•Press the [#] key to move the cursor to the left to make
any changes that may be needed.
•When entry is complete press the [*] key until the cursor
is at the far right position.
•To accept all of the clock information, press the [*] key
again.
Honeywell Proprietary
Vista-20P Series
Security Codes
 Honeywell.com
Security Codes
Vista-20P supports up to 48 user codes
which can be assigned one of 5 authority levels.
Vista-15P supports up to 33 user codes
which can be assigned one of 4 authority levels.
Vista-10P supports up to 16 user codes
which can be assigned one of 4 authority levels.
Honeywell Proprietary
 Honeywell.com
Security Codes
Authority Levels
(authority levels can be assigned to users 03-49 only; users 1 and 2 cannot be changed.)
Level
User No.
Functions
Installer
01
Perform all security functions except can disarm only if used to arm;
can enter program mode; cannot change installer code (default4112)
System
Master
02
Only one system master code per system; can perform all security
functions, add/delete users in either partition, change master code,
view event log, set system clock, program keypad macro, program
scheduled events, activate output devices (triggers/relays) (default1234)
Partition
Master
(default)
P1 = 03
P2 = 33
Same as master, except add/delete users limited to assigned
partition only
Honeywell Proprietary
 Honeywell.com
Security Codes
Authority Levels
(authority levels can be assigned to users 03-49 only; users 1 and 2 cannot be changed.)
Level
User No.
Functions
0-User
03-49
Perform security functions (arm, disarm,etc) only; cannot add/delete
users, view event log, set system clock or program scheduled events.
1-Arm only
03-49
Arm system only
2- Guest
03-49
Can disarm the system only if it was used to arm the system
3-Duress
03-49
Performs security functions, but also silently sends a duress message
to the central station; reports as zone 92
4-Partition
Master
03-49
Used to assign other user numbers as partition masters
Not used for the Vista-15P and Vista-20P
Honeywell Proprietary
 Honeywell.com
Security Codes
Adding a User Code:
Master code + [8] + 2-digit user no. + user’s code
Deleting a User Code: Master code + [8] + 2-digit user no. + [#] [0]
Assigning Attributes:
Master code + [8] + 2-digit user no. + [#] [attribute no] + value
Attributes:
Values
1=Authority Level
2=Access Group
3=Active Partition
for this user;
4=RF Zone No.
0-4 (see Authority Level table)
0-8 (0= not assigned to a group)
1,2,3 (common)
5=Open/Close paging
Assigns user number to button type
zone for arm/disarm
1 for yes; 0 for no
Honeywell Proprietary
 Honeywell.com
Review
•
•
•
•
What is the maximum number of zones?
Do the keyfob zones count in the above number?
How many programmable outputs does each panel offer?
Do all ECP devices (keypads, expanders, etc.) need to have a
unique address?
• Can we program a relay to activate in *79 output device
mapping?
Honeywell Proprietary
http://www.security.honeywell.com/hsc/
and click on MyWebTech
User name: honeywell
Password: support99
Honeywell Security support e-mail: [email protected]

similar documents